Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 6 of 10)
is
Code + Description | Possible cause | Solution | Remark | ||
|
|
|
|
| |
F05 (lock out error) | Incorrect roof or wall | 1. | Check that the correct roof or wall terminal has been fitted. See | If the error cannot be resolved or is persistent, contact your | |
Too many flame errors | terminal. |
| ’3.9 Air supply and flue gas discharge’. | installer. | |
Recirculating flue |
|
|
| ||
have been signalled. | 2. | If necessary, install the correct roof or wall terminal. |
| ||
| gases. | 3. | Check that the roof or wall terminal discharges into a permitted |
| |
|
|
| |||
|
|
| area. |
| |
|
|
|
| ||
F06 (lock out error) | Damaged cable in | Check the wiring of the ionisation rod. If necessary, replace the | If the error persists, contact your installer. | ||
Short circuit between | contact with metal | wiring. | To replace the necessary parts, you must contact your installer. | ||
ionisation rod and | surface. |
|
|
| |
earth |
|
|
|
| |
Ceramic part of the | 1. | Check whether the ceramic part of the ionisation rod is still |
| ||
|
| ||||
| ionisation rod is |
| intact, in the vicinity of the air distribution plate of the burner. |
| |
| broken/cracked. | 2. | If this is not the case, the ionisation rod must be replaced. |
| |
|
|
| |||
|
|
|
|
| |
F07 (lock out error) | Defective gas valves. | 1. | Check whether there is still burner pressure present, after the | If the error cannot be resolved or is persistent, contact your | |
A flame has been |
|
| gas valves have closed. | installer. | |
|
|
| To replace the necessary parts, you must contact your installer. | ||
detected after the gas |
| 2. | Check whether a flame is still present, after the gas valves | ||
valve was closed. |
|
| have closed. |
| |
|
| 3. | If this is the case, then the gas control must be replaced. |
| |
|
|
|
|
| |
F08 (lock out error) | Flame detection | 1. | Reset ThermoControl. | If the error cannot be resolved or is persistent, contact your | |
Error message from | before gas valve | 2. | If the error appears again, replace ThermoControl. | installer. | |
opened. | To replace the necessary parts, you must contact your installer. | ||||
safety relay. |
|
| |||
|
|
|
|
|