Agilent Technologies E2050-90003 manual Troubleshooting Client Connections, Chapter

Models: E2050-90003

1 110
Download 110 pages 29.08 Kb
Page 95
Image 95
Manual background

Troubleshooting

Troubleshooting Client Connections

This indicates the client was unable to contact the Gateway. The Gateway may be on a different subnet than the client (see your Network Administrator) or the Gateway may have incorrect network configuration values.

nFor an HP-UX client system, type: ping hostname (or) IP_address Return. For example:

>ping E2050.agilent.com

PING E2050.agilent.com: 64 byte packets

64bytes from 128.10.0.3: icmp_seq=0. time=8. ms

64bytes from 128.10.0.3: icmp_seq=1. time=3. ms

64bytes from 128.10.0.3: icmp_seq=2. time=3. ms

64bytes from 128.10.0.3: icmp_seq=3. time=3. ms

Each line after the PING line is an example of a packet successfully reaching the Gateway. If, after several seconds, ping does not print any lines, use Ctrl+C to kill ping. The ping command will then report on what it found.

For example, the following indicates the client was unable to contact the Gateway. The Gateway may be on a different subnet than the client (see your Network Administrator) or the Gateway may have incorrect network configuration values

----E2050.agilent.com PING Statistics----

7 packets transmitted, 0 packets received, 100% packet loss

2For an HP-UX client system ONLY, once ping works, you can try one of the following rpcinfo commands using the Gateway IP address to verify that the client has access privileges to the Gateway (in the IP allow list configuration):

n rpcinfo -p IP_address Return. This rpcinfo command gives the following response, where the line for program 395180 is the LAN server in the Gateway.

program

vers

proto

port

 

100000

2

tcp

111

portmapper

100000

2

udp

111

portmapper

395180

1

tcp

5055

 

Chapter 5

95

Page 95
Image 95
Agilent Technologies E2050-90003 manual Troubleshooting Client Connections, Chapter