9.0 Wind Turbine Operation | 69 |
9.1.1 Turbine TEST/OFF/ON
Turbine OFF:
This is the normal OFF mode. All brakes are deployed with the brake relays
Turbine ON:
This is the normal ON mode. The PLC continuously monitors the system parameters for wind turbine readiness and for fault conditions.
In the absence of faults, the wind turbine is in the ready mode and the ready light will be ON. At low wind speeds the brake light will be ON indicating that the wind turbine is parked. When the wind speed average is above 4.9 m/s (11 mph) the PLC will release the brakes allowing the turbine to freewheel up to speed and come on line as follows:
∙The brake relays are energized.
∙The tip brake magnets are energized and hold the tip brake plates closed.
∙The dynamic brake relay is energized, disconnecting the dynamic brake resistors and capacitors from the generator output.
∙The parking brake solenoid is energized, releasing the
∙In sufficiently strong winds the wind turbine freewheels up to speed and is monitored by the controller.
∙When the
If the wind speed average drops below 3.6 m/s (8 mph), the wind turbine will go through a normal shutdown procedure as follows:
∙The main contactor disconnects from the grid.
∙The tip brake and dynamic brake relays deploy.
∙The brake light lights up.
∙The parking brake relay deploys after 4 seconds.
∙The brake cooling cycle light lights up; the cooling cycle typically runs for 15 minutes.
The brake cooling cycle allows the dynamic brake resistors and parking brake to cool to ambient temperatures. During this period, the PLC overrides the wind speed sensor, thereby preventing the wind turbine from reconnecting to the grid. At the end of the cooling cycle, the PLC reverts to the normal control mode with the wind turbine ready light ON.