9.0 Wind Turbine Operation

76

9.1.7.1 PLC Inputs

The following tables list and describe the input signals to the PLC controlling the AOC 15/50.

Function

 

Description

 

 

 

Anemometer #1

0-5

VDC analog signal corresponds to 0-45 m/s (0-100 mph).

 

 

 

Anemometer #2

0-5

VDC analog signal corresponds to 0-45 m/s (0-100 mph).

 

 

Generator speed proximity

Pulse input to F/V converter. 1-5 VDC signal corresponds to 0

switches #1 and #2

to 2,000 rpm.

 

 

 

Watts Transducer Control

0-5

VDC analog signal corresponds to 0-8 kW.

 

 

 

 

 

 

Table 9.1-6 PLC low level analog inputs

 

Function

 

Description

 

 

Generator thermal switch

3 series connected switches within the generator.

 

 

 

Grid Voltage monitor

 

Relay contact indicating loss of phase, phase reversal and under

 

 

 

or over voltage.

 

 

 

 

Grid

Frequency

monitor

Relay contact indicating over or under frequency.

(optional)

 

 

 

 

 

Master control relay

 

Used to determine whether or not the turbine has been reset.

 

 

Turbine OFF/TEST/ON

Maintained switch parks or starts the turbine. In test position it

 

 

 

allows special test functions to become active.

 

 

 

Rotor jog switch

 

Maintained switch releases the brakes and connects the turbine

 

 

 

to the grid. Available in test mode.

 

 

Parking brake release switch

Maintained switch releases the parking brake. Available in test

 

 

 

mode.

 

 

Dynamic brake test switch

Maintained switch used in combination with the rotor jog

 

 

 

switch to delay operation of the tip and parking brakes to verify

 

 

 

the effectiveness of the dynamic brake. Available in test mode.

 

 

Remote start (optional)

Allows a turbine to be started by another turbine's controller; its

 

 

 

own anemometers (if equipped) are ignored.

 

 

Remote line start (optional)

Causes an across the line start if remote start is true.

 

 

 

 