9.0 Wind Turbine Operation | 73 |
|
| Table |
|
|
|
Function | Color | Description |
Turbine Ready | Green | ON: Turbine can be connected to the utility network. |
Turbine On | Green | ON: Turbine is connected to the utility network. |
Line |
|
|
Brakes Applied | Red | ON: Any of the brakes are deployed. |
|
| OFF: When parking brake is released during parking brake release |
|
| test. |
Brake Cooling | Red | ON: Turbine is waiting for brakes to cool (typically 15 minutes). |
Cycle |
|
|
|
| FLASHING: Parking brake undercurrent fault. Must be reset |
|
| manually. |
Grid Fault | Red | ON: Monitor detected over/under voltage, phase reversal, loss of |
|
| phase. Stays on for duration of brake cooling cycle. |
Generator | Red | ON: Generator internal thermal switch indicates an elevated |
Thermal Alarm |
| temperature. Must be reset manually. |
|
| FLASHING: Softstart thermal switch indicates an elevated |
|
| temperature. Must be reset manually. |
Rotor | Red | ON: Maximum rotor speed exceeded (1875 rpm for 60 Hz). Must |
Overspeed |
| be reset manually. |
|
| FLASHING: Difference of over 20 rpm between the two speed |
|
| sensors. This does not shut down the turbine. |
Rotor | Red | ON: Generator maximum power rating exceeded (1550 rpm for |
Overpower |
| 50 Hz and 1860 rpm for 60 Hz ). |
High Wind | Red | ON: Wind speed has exceeded program limit (typically 22.3 m/s or |
Speed |
| 50 mph). Stays on for duration of brake cooling cycle. |
|
|
|
|
|
|
Spare | Red | ON: Low power shut down. Turbine power output is low for giving |
|
| wind speed. |
|
| FLASHING: Three low power shut downs have occurred within |
|
| 75 minutes. Must be reset manually. |
|
|
|
|
|
|
NOTICE: Use of the material contained in this document is subject to the warning on page Iv and the disclaimer on page v of this document.
DOC012R02 | AOC 15/50 User Manual | Nov 2001 |