9.0 Wind Turbine Operation | 70 |
The PLC monitors the system parameters continuously as shown in Table
During any fault related shutdown, the tip and dynamic brakes activate immediately, with the dynamic brake providing a large portion of the braking torque. Application of the parking brake is normally delayed until the rotor has slowed down sufficiently using the tip and the dynamic brakes. During a loss of utility power to the controller, all brakes are applied simultaneously. Thirty three percent of the dynamic brake capacitance is disabled to allow an immediate torque contribution by the parking brake, keeping the overall braking torque within safe limits.
Turbine TEST:
When set to TEST the parking brake, dynamic brake and rotor jog switches can be energized.
9.1.2 Heater ON
The generator winding and the parking brake heaters prevent condensation from collecting on the windings and the parking brake, respectively. They can be activated manually at the operator's discretion when the dew point is high but only when the wind turbine is disconnected from the grid. When the main contactor is closed, the PLC automatically
9.1.3 Parking Brake Release
The parking brake release switch allows the operator to release the parking brake when the wind turbine is in test mode and no grid faults,
NOTICE: Use of the material contained in this document is subject to the warning on page Iv and the disclaimer on page v of this document.
DOC012R02 | AOC 15/50 User Manual | Nov 2001 |