9.0 Wind Turbine Operation

 

 

 

 

71

 

 

 

 

 

 

 

 

Instrumentation

60hz

50hz

action

reset when cleared

status lights

Grid parameters

grid monitor

 

 

 

 

 

over voltage:

 

400-540V

350-450V

disconnect and park

automatic

grid monitor light

under voltage:

 

380-460V

300-400V

disconnect and park

automatic

grid monitor light

(response time)

 

adj 1-10secs

adj 1-10secs

 

 

 

phase loss

 

 

 

disconnect and park

automatic

grid monitor light

 

 

 

 

 

 

 

phase reversal

 

 

 

disconnect and park

automatic

grid monitor light

 

 

 

 

 

 

 

Rotor Speed

2 speed sensors on

 

 

 

 

 

 

high speed shaft

 

 

 

 

 

Rotor nominal:

 

1800rpm

1500rpm

if no faults connect to grid

 

turbine on line

Rotor full load:

 

1840rpm

1535rpm

 

 

 

Rotor overpower:

 

1860rpm

1550rpm

disconnect and park

automatic

rotor overpower

Rotor over-speed

 

1875rpm

1560rpm

disconnect and park

manual

rotor overspeed

Rotor under-speed:

 

1760rpm

1460rpm

disconnect and park

automatic

 

(freewheel option)

 

1800rpm

1500rpm

disconnect and freewheel

automatic

 

(coast up option)

 

< 50rpm after 1 min?

< 50rpm after 1 min?

disconnect and park

automatic

rotor overspeed flashing

 

 

 

 

 

 

 

Wind Speed

2 anemometers

 

 

 

 

 

wind in range

 

11mph - 50mph

11mph - 50mph

if no faults release brake

 

 

low wind

 

8mph

8mph

disconnect and park or freewheel

automatic

 

high wind

 

50 mph

50 mph

disconnect and park

automatic

high wind speed

 

 

 

 

 

 

 

Power output

watts transducer

 

 

 

 

 

low power

 

% < set points

% < set points

disconnect and park

automatic

 

 

 

from power curve

from power curve

 

 

 

 

 

 

 

 

 

 

Brake status

 

 

 

 

 

 

brakes applied

plc signal

 

 

disconnect and park

automatic

brakes applied

parking brake fault

current sensor

 

 

disconnect and park

manual

brakes applied flashing

 

 

 

 

 

 

 

Generator Temperature

3 NC thermostats

 

 

 

 

 

over temperature

 

145 deg C

145 deg C

disconnect and park

automatic

generator thermal alarm

Table 9.1-2 PLC control system monitoring

NOTICE: Use of the material contained in this document is subject to the warning on page Iv and the disclaimer on page v of this document.

DOC012R02

AOC 15/50 User Manual

Nov 2001

Page 79
Image 79
AOC 15 user manual PLC control system monitoring