Chapter 1 Preparing for Installation

Site Requirement Guidelines

NEBS Supplemental Unit Bonding and Grounding Guidelines

Although the router chassis requires a safety earth ground connection as part of the power cabling to power modules, you must permanently connect the central office ground system or interior equipment grounding system to the supplemental bonding and grounding connection on the side of the router chassis to meet network equipment building system (NEBS) requirements as well as safety compliance requirements. These grounding points are referred to as the NEBS bonding and grounding points.

Figure 1-22shows the NEBS grounding locations for the Cisco ASR 9001 Router.

Note These bonding and grounding connections satisfy the Telcordia NEBS requirements for supplemental bonding and grounding connections. If you are not installing the router in a NEBS environment, you can choose to bypass these guidelines and rely on the safety earth ground connections to the AC or DC power modules.

Figure 1-22 NEBS Bonding and Grounding Points on the Cisco ASR 9001 Router

1

332017

1NEBS grounding point on side of chassis

To ensure a satisfactory supplemental ground connection to the router, use these parts:

One grounding lug, which has two M6 bolt holes with 0.625- to 0.75-inch (15.86- to 19.05-mm) spacing between them, and a wire receptacle large enough to accept a six AWG or larger, multistrand copper wire. For four AWG cable, use Panduit part number LCD4-14AF-L; for six AWG, use Panduit part number LCD6-14AF-L.

Two 10-32 round-head screws and two locking washers (nickel-plated brass is ideal).

 

Cisco ASR 9001 and Cisco ASR 9001-S Routers Hardware Installation Guide

1-20

OL-26701-02

Page 30
Image 30
Cisco Systems 9001S, ASR9001s manual Nebs Supplemental Unit Bonding and Grounding Guidelines