Error Code | Message Information |
|
|
PSU0034 | Message | An under voltage fault detected on power supply <number>. | |
| |||
| LCD Message | An under voltage fault detected on PSU <number>. Check power | |
|
| source. | |
| Details | This failure may be the result of an electrical issue with cables or | |
|
| subsystem components in the system. | |
| Action | 1. | Remove and reinstall the power supply. |
|
| ||
|
| 2. | Check cables and subsystem components in the system for |
|
|
| damage. |
|
| 3. | If the issue persists, see Getting Help. |
PSU0035 | Message | An over voltage fault detected on power supply <number>. | |
| |||
| LCD Message | Over voltage fault on PSU <number>. Check PSU. | |
| Action | Check input power or reinstall the power supply. If the issue persists, | |
|
| see Getting Help. | |
PSU0036 | Message | An over current fault detected on power supply <number>. | |
| |||
| LCD Message | An over current fault detected on PSU <number>. Check PSU. | |
| Details | This failure may be the result of an electrical issue with cables or | |
|
| subsystem components in the system. | |
| Action | 1. | Remove and reinstall the power supply. |
|
| ||
|
| 2. | Check cables and subsystem components in the system for |
|
|
| damage. |
|
| 3. | If the issue persists, see Getting Help. |
PSU0037 | Message | Fan failure detected on power supply <number>. | |
| |||
| LCD Message | Fan failure detected on PSU <number>. Check PSU. | |
| Action | Check for fan blockage. If the problem persists, see Getting Help. | |
PSU0076 | Message | A power supply wattage mismatch is detected; power supply | |
| |||
|
| <number> is rated for <value> watts. | |
| LCD Message | PSU wattage mismatch; PSU <number> = <value >watts | |
| Details | Power supplies should be of the same input type and power rating. | |
| Action | Install matched power supplies and review this manual for proper | |
|
| configuration. |