Wiring Instructions For A DC Power Supply
Your system supports up to two
WARNING: For equipment using
CAUTION: Wire the unit with copper only, unless otherwise specified, use only 10 American Wire Gauge (AWG) wire rated minimum 90 ºC for source and return. Protect the
CAUTION: Connect the equipment to a
NOTE: A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the field wiring.
Input Requirements
•Supply voltage:
•Current consumption: 32 A (maximum)
Kit Contents
•Dell part number 6RYJ9 terminal block or equivalent (1)
•
Required Tools
NOTE: Use alpha wire part number 3080 or equivalent (65/30 stranding)
Required Wires
•One UL 10 AWG, 2 m maximum (stranded) black wire
•One UL 10 AWG, 2 m maximum (stranded) red wire (V DC return)
•One UL 10 AWG, 2 m maximum green/yellow, green with a yellow stripe, stranded wire (safety ground)
Assembling And Connecting The Safety Ground Wire
WARNING: For equipment using
1.Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm (0.175 inch) of copper wire.
2.Using a
92