Dell E23S Series owner manual Gaseous Contamination

Models: E23S Series

1 157
Download 157 pages 61.09 Kb
Page 138
Image 138

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.

Air Filtration

NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.

NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

Conductive Dust

Air must be free of conductive dust, zinc whiskers, or

NOTE: Applies to data center and non-data center

other conductive particles.

environments.

 

Corrosive Dust

• Air must be free of corrosive dust.

 

NOTE: Applies to data center and non-data center

• Residual dust present in the air must have a

environments.

deliquescent point less than 60% relative humidity.

 

Gaseous Contamination

 

NOTE: Maximum corrosive contaminant levels measured at 50% relative humidity.

Copper Coupon Corrosion Rate

<300 Å/month per Class G1 as defined by ANSI/

 

ISA71.04-1985.

Silver Coupon Corrosion Rate

<200 Å/month as defined by AHSRAE TC9.9.

138

Page 138
Image 138
Dell E23S Series owner manual Gaseous Contamination