Configuring the DeviceNet Network

DN Network Status

Ei-DN

 

 

 

 

 

Modbus Address: 34207

Range

Units

Default

Type

DN Type

Group

 

NVM

Res.

Access

0-31

 

 

ENM

Word

 

 

No

 

RO

 

 

 

 

 

 

 

 

 

 

The DN Network status indicates the ODVA specific status of the DeviceNet network as follows:

 

Value

Network Status

 

1

No Power

 

 

 

 

2

Not Connected

 

 

 

 

3

Connected

 

 

 

 

4

Time-out

 

 

 

 

5

Link Failure

 

 

 

DN Receive Counter

 

Ei-DN

 

 

 

 

Modbus Address: 34203-34204

Range

Units

Default

Type

DN Type

Group

NVM

Res.

Access

0-231-1

Counts

 

US32

UDINT

 

No

 

RO

The DN Receive Counter keeps a running total of all DeviceNet packets successfully received from the Ei-DN on the DeviceNet network.

DN Status Major Recoverable Fault

Ei-DN

 

 

 

 

 

Modbus Address: 14003

Range

Units

Default

Type

DN Type

Group

 

NVM

Res.

Access

True/False

 

 

BIT

BOOL

 

 

No

 

RO

 

 

 

 

 

 

 

 

 

 

A Major Recoverable Fault disables the bridge and then re-enables the bridge when the fault has cleared. At the present, no Major Recoverable Faults are defined in the Ei-DN.

DN Status Major Unrecoverable Fault

Ei-DN

 

 

 

 

 

Modbus Address: 14004

Range

Units

Default

Type

DN Type

Group

 

NVM

Res.

Access

True/False

 

 

BIT

BOOL

 

 

No

 

RO

 

 

 

 

 

 

 

 

 

 

A Major Unrecoverable Fault is implemented on the Ei-DN when one of the following faults occur: Power Stage Module, Invalid Configuration, Power Up Self Test, NVM Invalid, Motor Overtemp, Drive Overtemp, Duplicate MacID, and Bus-Off. Major Unrecoverable Faults disable the bridge and require a cycle of power to reset.

29