Configuring the DeviceNet Network

Accessing the EDS File

The EDS file is used for configuration of the DeviceNet master. This file tells the Master software how much I/O data is supported for a particular DeviceNet device as well as Control Techniques’ vendor code, module revision, etc. The EDS file for the Ei-DN also contains the Class, Instance, and Attribute ID’s for all Ei drive parameters. These class, instance, and attribute ID’s are used for explicit messaging and can be found in the back of this manual in the Drive Parameters chapter.

The EDS file is installed with PowerTools FM and can be found in the PTOOLSFM folder. An icon file is also located in this section for display on the master software configuration screen. These two files may also be downloaded from our website at www.emersonct.com.

Hardware Interface

Module Status LED

The Module Status LED located on the front of the drive provides device status according to the following table:

LED State

Drive State

Indicates

Off

No Power

There is no power applied to the device.

 

 

 

Green

Device Operational

The device is operating in a normal condition.

 

 

 

Flashing Green

Device in Standby (The Device Needs

The device need commissioning due to configuration missing,

Commissioning)

incomplete, or incorrect. The Device may be in the standby state.

 

 

 

 

Flashing Red

Minor Fault

Recoverable Fault

 

 

 

Red

Unrecoverable Fault

The device has an unrecoverable fault; may need replacing

 

 

 

Flashing Red-

Device Self Testing

The device is in self-test.

Green

 

 

 

 

 