UPS Interconnection Kits
Appendix A.2.4 Liebert FS Configuration - Single Liebert FS on Liebert Series 610/600T/600 DC Bus
The following Software Control Parameters must be set when the Liebert FS is connected to the DC bus of the Liebert Series 610/600T/600 UPS system.
NOTE
The Software Control Parameter values specified below are recommended. These values may require adjustments due to the battery type. These must be used unless otherwise specified by the
Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System Startup.
Table 20 Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter | Setting |
|
|
Charge Voltage | 530VDC |
|
|
Regulation Voltage | 520VDC |
|
|
Vreg Delta | 0VDC |
|
|
Maximum Charge Current | See Table 21 |
|
|
Charge Amps/Volts | See Table 21 |
|
|
Table 21 Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA) | 65 | 80 | 100 | 125 | 150 |
|
|
|
|
|
|
Liebert FS Maximum Charge Current (A) | 25 | 31 | 39 | 49 | 50 |
|
|
|
|
|
|
Liebert FS Charge Amps/Volts (A/V) | 1.7 | 2.1 | 2.6 | 3.3 | 3.4 |
|
|
|
|
|
|
Appendix A.2.5 Liebert FS Configuration - Multiple Liebert FS Units on Liebert Series 610/600T/600 DC Bus
The Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are con- nected in parallel on the DC bus of a Liebert Series 610/600T/600 UPS system.
Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System Startup.
Multiple Liebert FS Parallel Operation - Regular Configuration with Liebert Series 610/ 600T/600
The Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are con- nected in parallel on the DC bus of a Liebert Series 610/600T/600 UPS system for proper operation with longer run times or higher backup power requirements. The Liebert FS units will contribute all together at the same time to the task of supporting the UPS DC bus.
NOTE
This configuration is recommended for UPS models with output power levels greater than 150 kVA (i.e., 225, 300, 400, 450, 500, 625, 750 and 1,000 kVA).
NOTE
In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales representative to arrange a review of the application.
NOTE
Your