Troubleshooting

Table 15 lists the warnings and some troubleshooting steps that may be taken if any of the Warnings in appear.

Table 15 Warnings

Warning

Meaning / Possible Causes

Troubleshooting

Label

 

 

AUXPOWER

Auxiliary power supply is low when the system is

 

not in OFF mode.

Check / Test Auxiliary power supply

LOW

Factory-configurable warning

 

 

 

 

 

 

VACUUM

Drag power exceeds 85W *

Check Vitals and Vacuum History

LOW

 

 

MISER HIGH

Miser voltage is higher than 2V

Calibrate board

 

 

 

RUNOUT

Runout is higher than 2.0 mil.*

Check Vitals and Runout History

HIGH

 

 

PWR SPLY

Power supply for PPMC/PCMC is lower than 21V.

Power supply for PPMC/PCMC is lower

VOLT LOW

than 21V

 

VIB

VIB inoperative while enabled

Check VIB cable connections and wiring

INOPERATIVE

 

 

OVERSPEED

Speed is higher than the Max Speed

Have Certified Service personnel check

software settings

 

 

SET TIME/

Time and date have not been set

Set Time/Date in Menu>View>Time/Date

DATE

 

 

* Warnings of this nature should be monitored and may be used to schedule preventive maintenance.

If Warnings persist, contact your local Liebert representative or contact Liebert Services at 800-543- 2378. You may also visit the Liebert Web site for information at www.liebert.com.

NOTE

A “Standby, Motor Hot” message may be displayed as a result of consecutive and repetitive discharges. This is not a Warning but a normal operating occurrence that may occur due to frequent charging and discharging of system. Once motor cools it will automatically resume operation.

80