Auxiliary Backup AC Power Supply

Appendix F.3.2 Operating the Liebert FS Without Batteries

If the Liebert FS is operating without batteries, Liebert recommends feeding the backup AC power supply from a separate, protected supply. This may be the output of another UPS or a supply from a separate feeder circuit (see Figures 158 and 159).

Figure 158 Two Liebert FS units operating in a paralleled for capacity (not redundancy) configuration, with a UPS and without batteries attached to the DC bus

 

 

Grid

 

 

Supply

Fed from a

 

 

 

BACKUP AC

protected AC

POWER SUPPLY

supply, either

the output of

 

another UPS

 

or a separate

 

feeder supply

 

UPS

DC Bus

 

 

 

 

UPS

 

 

 

 

 

Output

Fed from a

 

 

 

 

 

 

 

 

BACKUP AC

protected AC

 

 

 

POWER SUPPLY

supply, either

 

 

 

 

 

the output of

 

 

 

 

 

another UPS

 

 

 

 

 

or a separate

 

 

 

 

 

feeder supply

Liebert FS

Liebert FS

Figure 159 Multiple Liebert FS units operating with a UPS and without batteries attached to the DC bus

 

 

UPS

Grid

 

 

 

 

 

 

 

 

 

 

 

 

UPS

Supply

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Distribution

 

 

 

 

 

 

 

 

 

panel*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC Bus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* NOTE:

Distribution panel allows3 Liebert FS Units removal of a Liebert FS without

disrupting the other units