Maintenance

7.4Maintenance Schedule

! WARNING

Any maintenance on the system should be delayed by at least 10 minutes after system is shut down to be certain all electronics have discharged. Use appropriate safety precautions to ensure unit is disconnected and de-energized.

! CAUTION

Unless specified otherwise, ONLY a Liebert-certified service technician should perform all maintenance work. Failure to use a Liebert technician for maintenance actions, unless specifically noted, may void your warranty.

The Liebert FS maintenance schedule consists of actions listed in Table 11.

Table 11 Maintenance schedule

 

 

Frequency

 

 

 

 

 

 

 

Service

 

Every

Every

Every

Every

Item/Action

1 yr

2 yrs

6 yrs

15 yrs

Performer

System Visual Inspection *

Check

Liebert/Owner

or Test

 

 

 

 

 

System Cleaning (if necessary)

Check

Liebert/Owner

or Test

 

 

 

 

 

System Testing

Check

Liebert

(and adjustments, if necessary)

or Test

 

 

 

 

PCM Capacitor Bank

Service or

Liebert

Replace

 

 

 

 

 

 

Once

Check

Service or

Liebert

Flywheel Module

after

or Test

Replace

 

Startup

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Interconnection Kit (if option installed)

Check

Liebert

or Test

 

 

 

 

 

Air Filter (if option installed)

Check

Liebert/Owner

or Test

 

 

 

 

 

NOTE

The recommended System Visual Inspection every year should include a check and torque of cabinet DC circuit breaker box lug connections and the DC ground; see the relevant section of Appendix A.0 - UPS Interconnection Kits for torque requirements.

NOTE

Liebert may determine additional maintenance actions as necessary and issue service or technical bulletins to address any additions.

NOTE

The optional inlet Air Filter in the cabinet will need to be replaced when it is sufficiently dirty to significantly reduce the flow of air into the cabinet. Ambient conditions at the installation site will determine the frequency of replacement if option is installed

7.5Record Log

Set up a maintenance log to record scheduled checks and any abnormal conditions.

The log should have space for all metered parameter indications including phase readings, alarm messages, mode of operation, air filter replacement date and observation notes.

A periodic walk-through inspection of the Liebert FS room is advised to check for visible and audible indications of problems. Log the inspection, metered parameter indications and any discrepancies.