Maintenance
7.4Maintenance Schedule
! WARNING
Any maintenance on the system should be delayed by at least 10 minutes after system is shut down to be certain all electronics have discharged. Use appropriate safety precautions to ensure unit is disconnected and
! CAUTION
Unless specified otherwise, ONLY a
The Liebert FS maintenance schedule consists of actions listed in Table 11.
Table 11 Maintenance schedule
|
| Frequency |
|
| ||
|
|
|
|
| Service | |
| Every | Every | Every | Every | ||
Item/Action | 1 yr | 2 yrs | 6 yrs | 15 yrs | Performer | |
System Visual Inspection * | Check | — | — | — | Liebert/Owner | |
or Test | ||||||
|
|
|
|
| ||
System Cleaning (if necessary) | Check | — | — | — | Liebert/Owner | |
or Test | ||||||
|
|
|
|
| ||
System Testing | — | Check | — | — | Liebert | |
(and adjustments, if necessary) | or Test | |||||
|
|
|
| |||
PCM Capacitor Bank | — | — | Service or | — | Liebert | |
Replace | ||||||
|
|
|
|
| ||
| Once | Check | — | Service or | Liebert | |
Flywheel Module | after | |||||
or Test | Replace | |||||
| Startup |
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
UPS Interconnection Kit (if option installed) | — | Check | — | — | Liebert | |
or Test | ||||||
|
|
|
|
| ||
Air Filter (if option installed) | Check | — | — | — | Liebert/Owner | |
or Test | ||||||
|
|
|
|
| ||
NOTE
The recommended System Visual Inspection every year should include a check and torque of cabinet DC circuit breaker box lug connections and the DC ground; see the relevant section of Appendix A.0 - UPS Interconnection Kits for torque requirements.
NOTE
Liebert may determine additional maintenance actions as necessary and issue service or technical bulletins to address any additions.
NOTE
The optional inlet Air Filter in the cabinet will need to be replaced when it is sufficiently dirty to significantly reduce the flow of air into the cabinet. Ambient conditions at the installation site will determine the frequency of replacement if option is installed
7.5Record Log
Set up a maintenance log to record scheduled checks and any abnormal conditions.
The log should have space for all metered parameter indications including phase readings, alarm messages, mode of operation, air filter replacement date and observation notes.
A periodic