System Overview

Following a User Command

In any mode, except OFF mode, the user may command the Liebert FS to transition in SHUTDOWN. While in SHUTDOWN mode, the user will still be able to command the Liebert FS to transition into CHARGE mode (if SOC > 0%) or STARTUP mode (if SOC < 0%), provided that the UPS System DC bus voltage is greater than Vcharge.

Figure 52 SHUTDOWN mode diagram - user-initiated shutdown

State of Charge < 0

State of Charge > 0

0%

991 .00% 5%

5.3.8COAST Mode

A transition into COAST mode can occur when the UPS System DC Bus voltage drops below Vcharge while the Liebert FS is in STARTUP mode. While in COAST mode, the Liebert FS is in an idling con- dition where it neither draws nor generates any power.

As soon as the UPS DC Bus Voltage rises above Vcharge, the Liebert FS will automatically exit COAST mode and resume STARTUP mode.

After five minutes in COAST Mode, if the UPS DC Bus voltage has not risen above Vcharge, the Liebert FS will automatically transition into SHUTDOWN Mode.

5.3.9FAULT Mode

The Liebert FS includes self-test and diagnostic circuitry such that most systems malfunctions can be identified. In case of a system malfunction, the Liebert FS will transition into FAULT mode.

While in FAULT mode, the Liebert FS is disabled—all power electronics are turned off. Most faults are cleared automatically by the system without the need for user intervention. Some faults do require user action to clear the fault or to notify Liebert Services. Refer to the 8.0 - Troubleshooting for more information).

NOTE

Depending on the nature of the fault, the Liebert FS may still be capable of supporting the UPS DC bus. Refer to 8.0 - Troubleshooting for more information.

The Liebert FS is programmed to operate in a variety of conditional modes. The modes and status for each mode will be indicated on the control panel. The Liebert FS is set up to transition through the various modes with no or minimal user intervention. Figure 53 illustrates the various modes of oper- ation.