Installation Drawings

 

 

 

 

 

 

 

 

 

 

Figure 147 Wiring specifications, Liebert FS and Liebert Series 610

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal

 

 

 

 

 

 

 

Wire

Designation

Signal

Maximum

Maximum

 

Wire Size

Maximum

Remarks

 

 

 

 

No.

From

To

Name

Voltage

Current

Color

& Type

Length

 

 

 

 

 

 

 

 

 

 

 

Liebert Series 610 UPS - Cable Group #16 (Flywheel CB IFM) From I1 in UPS Module to TB1 on Liebert FS Module

 

 

 

 

 

 

 

 

 

 

901

I1-TB1-1

TB1-1

Trip Signal (+)

+24 VDC

100mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

902

I1-TB1-2

TB1-2

Trip Signal (-)

-24 VDC

100mA

 

1/C #16 (2.5 mm2)

500 Ft

 

903

I1-TB1-7

TB1-7

Aux Comm

24 VDC

100mA

 

Stranded

(150 M

 

 

 

 

 

 

 

 

 

 

 

904

I1-TB1-8

TB1-8

Aux N.O.

24 VDC

100mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert Series 610 UPS - Cable Group #116 Flywheel Aux Power, Customer-Provided to Liebert FS TB1 on Fused

Disconnect

914

FBO

TB1-1

Line

120VAC

3.5A

 

 

 

UPS-

 

 

 

 

 

 

 

1/C #16 (2.5 mm2)

 

Protected

915

FBO

TB1-2

Neutral

120VAC

3.5A

 

500 Ft

 

 

 

 

 

 

 

Stranded

(150m)

Auxiliary

916

FBO

TB1-3

GND

120VAC

3.5A

 

Power

 

 

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Each cable group must be run in a separate, grounded, rigid metal conduit to prevent control signal interference.

2.Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.

3.All external wires furnished by others.

4.N.O. = Normally Open; N.C. = Normally Closed; Comm = common; F.B.O. = Furnished By Others, GND = ground

5.All wiring must be in accordance with national and local electrical codes.

Dwg. No. Control_WL_S610_Liebert-FS Rev. 01

139

DISCONTINUED

 

PRODUCT

Page 151
Image 151
Emerson 540VDC manual Wiring specifications, Liebert FS and Liebert Series