Operation

6.4.10Network—Requires DCM Option

The Network view screen displays the addresses of the DCM. Static address settings can be entered using the keypad into this screen. If this option is installed, reference the Liebert Data Collection Module (DCM) Option Manual for more information on setting up the DCM on a network and or assigning IP addresses. Figure 78 shows the Network screen in a read-only mode.

Figure 78 Networks view

>>

DHCP:

ON

 

>>

IP ADDRESS:

192.168.1.155

 

>>

NET MASK:

255.255.255.0

 

>>

DEFAULT GATEWAY:

192.168.1.1

 

>>

DNS SERVER:

192.168.1.13

 

 

 

HOME

DONE

By entering a Password to access the User level mode (see 6.3.2 - Password), you can edit this func- tion. Pressing the EDIT button, F1, will place the system in the edit mode. The DHCP must be dis- abled or turned OFF to proceed with setting IP addresses and other settings. After pressing EDIT you will see up/down arrows next to the DHCP ON value. Pressing the up or down arrows on the keypad will allow you to turn OFF or ON this function.

Figure 79 Networks view, Edit DHCP

>>

DHCP:

ON

 

>>

IP ADDRESS:

192.168.1.155

 

>>

NET MASK:

255.255.255.0

 

>>

DEFAULT GATEWAY:

192.168.1.1

 

>>

DNS SERVER:

192.168.1.13

 

EDIT

 

HOME

DONE

Once you have turned DHCP OFF, press EDIT again and now you will see numbers next to each of the settings. Pressing the corresponding number will allow you to enter or change that value. At any time you may press CANCEL to cancel the changes. Once the changes or entries are complete, press APPLY to complete entry process. Pressing APPLY will reboot system and in a few minutes the sys- tem will display the new screen.

Figure 80 Networks view, Edit Settings (Service level)

>>

DHCP:

ON

 

>>

IP ADDRESS:

192.168.1.155

 

>>

NET MASK:

255.255.255.0

 

>>

DEFAULT GATEWAY:

192.168.1.1

 

>>

DNS SERVER:

192.168.1.13

 

CANCEL

HOME

DONE

65