UPS Interconnection Kits

Appendix A.5 Installing the Liebert FS With a Liebert HiPulse UPS

The Liebert HiPulse UPS interconnection kit for the Liebert FS is compatible with the Liebert HiPulse™ models in Table 28.

Table 28 Liebert HiPulse model ratings

UPS Output Rating

kVA

80

120

160

200

300

400

500

600

800

 

 

 

 

 

 

 

 

 

 

kW

64

96

128

160

240

320

400

480

640

 

 

 

 

 

 

 

 

 

 

Appendix A.5.1 Description—HiPulse UPS Interconnection Kit

HiPulse UPS interconnection kit is composed of:

DC Power Interface

One Thermal-Magnetic Molded Case circuit-breaker rated for 250 ADC, 600VDC equipped with auxiliary contacts: two (2) sets of Normally Open (NO) and Normally Closed (NC).

Status/Control Interface

One Status/Control Terminal Block used to ensure the status/control connections between the Liebert FS and the Liebert HiPulse.

Appendix A.5.2 Status/Control Connections—Liebert HiPulse UPS Interconnection Kit

The status/control interface of the IKIT-A05 is the Status/Control Terminal Block. The connection of the Status/Control Terminal Block is illustrated in Figure 102. Please refer to this drawing to ensure that the proper connections are made. In case multiple Liebert FS units are connected to the same UPS DC bus, please refer to Figure 144 to perform the Status/Control connections between each Liebert FS.

This IKIT includes Status/Control Connections that enable transfer of “IKIT circuit-breaker status (closed/open)” signals between the Liebert FS system(s) and the UPS system.

Figure 102 Liebert HiPulse status/control terminal block wiring

 

 

 

 

Y

 

 

 

 

Y

 

 

 

 

e

 

 

 

 

e

B

 

 

l

B

 

 

l

l

 

 

l

 

l

 

 

l

u

 

o

u

 

o

e

 

w

e

 

w

 

 

 

Yellow/

 

 

 

 

 

Yellow/

 

 

 

 

 

 

 

 

 

 

 

 

 

Blue

 

 

 

 

 

Blue

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two rows

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10

Row for

installation of contractor wire connections

The recommended gauge for Status/Control Connection wires is 16 AWG – 600 VDC (approximate metric equivalent: 1.3 mm² wire section). All wiring must comply with all applicable local, regional, national regulations.

96

DISCONTINUED

 

PRODUCT

Page 108
Image 108