Emerson 540VDC manual System Mode Indicators, System Status Indicators, Operation modes

Models: 540VDC

1 168
Download 168 pages 31.68 Kb
Page 67
Image 67

Operation

6.2.2System MODE Indicators

The Liebert FS has nine modes of operation: OFF, STARTUP, CHARGE, READY, DISCHARGE, SHUTDOWN, COAST, FAULT and STANDBY. These are displayed on the main screen of the control panel as identified in Figure 55. Table 5 lists the system Modes along with the corresponding Con- tactor Status, and the Conditions required to operate in these Modes: external voltage range, speed and command.

NOTE:

See 5.3 - Modes of Operation for further details on modes of operation.

Table 5

Operation modes

 

 

 

 

 

 

 

 

 

 

 

 

Condition

 

Mode

 

Contactor

 

 

 

 

External Voltage

Speed

Command

 

 

 

 

 

 

OFF

 

Open

Vext < Vchg

0 ~ 3500

 

 

 

 

 

STANDBY

Open

Vext > Vchg

0 ~ 200

 

 

 

 

 

 

STARTUP

 

Close

Vext > Vchg

200 ~ Min Speed

STARTUP

 

 

 

 

 

 

CHARGE

 

Close

Vext > Vchg

Min Speed ~ Max Speed

STARTUP

 

 

 

 

 

 

READY

 

Close

Vext > Vchg

Max Speed ~ Max Speed + 200

STARTUP

 

 

 

 

 

DISCHARGE

Close

Vext < Vchg

Min Speed ~ Max Speed

STARTUP

 

 

 

 

 

 

COAST

 

Close

330 < Vext < Vchg

200 ~ Min Speed

STARTUP

 

 

 

 

 

SHUTDOWN

Open

Vext < 330

200 ~ Min Speed

STARTUP

 

 

 

 

 

 

 

 

Open

Any

Min Speed ~ Max Speed

SHUTDOWN

 

 

 

 

 

 

 

 

Close

Vext > 330

200 ~ Min Speed

SHUTDOWN

 

 

 

 

 

 

FAULT

 

Open

Any

0 ~ Max Speed

 

 

 

 

 

STANDBY

 

After CLRFLT

 

 

 

 

 

 

 

Min Speed: Minimum operating speed; State of Charge (SOC) will be 0% at this speed.

Max Speed: Maximum operating speed; State of Charge (SOC) will be 100% at this speed.

6.2.3System STATUS Indicators

The Liebert FS system displays multiple status conditions during operation. Table 6 shows the com- plete list of status indicators for the Liebert FS and the corresponding condition.

Table 6 System status indicators

 

Message

Condition

 

 

 

1

OK

All systems operating normally.

 

 

 

2

READY

All systems operational and ready for startup.

 

 

 

3

APPLY 520*V

External voltage is less than the Charge Voltage*

 

 

 

4

n WARNINGS

Multiple warnings

 

 

 

5

n FAULTS

Multiple faults

 

 

 

6

OVERSPEED

Speed is higher than the Max Speed plus 200 RPM

 

 

 

7

TESTING VACUUM

Vacuum testing at 10000 RPM

 

 

 

8

OPENING CONTACTOR

Waiting until the current is stabilized

 

 

 

9

CLOSING CONTACTOR

Waiting until the voltages are stabilized

 

 

 

10

WAIT

Waiting until the voltages are stabilized

 

 

 

* Charge voltage is an adjustable user parameter; 520V is used only as an example.