Unloading and Unpacking

5.Use a forklift to remove the cabinet from the shipping pallet.

To lift the Liebert FS, the forks should be inserted between the caster wheel assemblies (see Figure 10). Forks must be extended to the full depth of the cabinet—at least 6 ft. (2m) fork length—to properly support the equipment (see Figure 10). This likely requires fork extenders. The Liebert FS unit can weigh up to 1,300 lb. (590kg) and must be handled with care.

Figure 10 Lifting the Liebert FS cabinet

Forks must be

extended the full depth of the

cabinet

6.Unbolt and remove the two metal support plates (one on either side of the pallet).

Figure 11 Removing the metal support plates

Metal support

plate

Caster

(for moving short distances)

Leveling foot (one on each corner)

NOTE

Retain the four bolts (1/2" diameter x 1-3/4" long; 12.7mm diameter x 44.5mm long) attaching the metal support plates to the cabinet. These will be used to attach brackets to the cabinet for surface mounting.

7.Examine the Liebert FS internally and externally for transit damage. Report any damage to the shipper, your local Liebert representative and Liebert immediately.

! CAUTION

Do not attempt to install the system if there is any damage.

8.Check visually for loose connections and unsecured components in the cabinet.

9.You will find the installation manual, operation manual and options manual (if any) enclosed in the pocket inside the cabinet door (see Figure 12).

10.You will find the serial number and model number plate mounted on the cabinet door pocket or on the upper right corner of the face of the cabinet frame inside the door (see Figure 12). Record the model number and serial number in Table 1 - System information.