Troubleshooting

Faults. Table 17 - Troubleshooting describes actions that may alleviate the condition or provide valuable information for technical support.

Table 16 Faults—causes and responses

 

 

Operator

Auto

Auto

Fault Label

Meaning / Possible Causes

Clear*

Clear

Shutdown

 

 

 

 

 

GROUND FAULT

Ground fault current out of range.

X

 

 

 

 

 

 

 

HW BUS OV

HW overvoltage. (hardware protection)

X

 

 

 

 

 

 

 

X PHASE OC

AC phase overcurrent. x = A, B, C.

X

 

 

 

 

 

 

 

IGBT OVRTEMP

IGBT overtemperature.

X

 

 

 

 

 

 

 

VACUUM FAULT

Drag power exceeds 125W.

 

 

X

 

 

 

 

 

RUNOUT FAULT

Runout higher than 2.9mil.

 

 

X

 

 

 

 

 

MISER FAULT

Miser voltage is higher than 5V.

 

 

X

 

 

 

 

 

BEARING

Magnetic bearing fault.

 

 

X

 

 

 

 

 

AUX POWER LOW

Auxiliary power supply voltage is low when the

X

 

 

system is in Off mode. Configurable fault.

 

 

 

 

 

 

INTER PRCR COMM

Communication error with secondary DSP. System

 

X

 

reboots.

 

 

 

 

 

 

PWR SPLY VOLT

Power supply voltage is lower than 19V. (Speed

X

 

X

dependent; auto shutdown at high speed)

 

 

 

 

 

UNDEF PDP INT

Undefined PDP interrupt.

X

 

 

 

 

 

 

 

CURRENT OFFSET

AC motor current sensor error.

X

 

 

 

 

 

 

 

SW OV

DC bus voltage is higher than the threshold, which is

X

 

 

service-configurable.

 

 

 

 

 

 

CHECKSUM

Calculated checksum does not match the stored

S

 

 

checksum.

 

 

 

 

 

 

CONTACTOR TIME OUT

Bus voltage/current is not stable while trying to close

X

 

 

or open contactor.

 

 

 

 

 

 

CONTACTOR CLOSE FAIL

Contactor failed to close on startup.

X

 

 

 

 

 

 

 

FAN OPEN

Fan open circuit or disconnected.

X

 

 

 

 

 

 

 

FAN SHORT

Fan short circuit.

X

 

 

 

 

 

 

 

PUMP OPEN

Pump open circuit or disconnected.

X

 

 

 

 

 

 

 

PUMP SHORT

Pump short circuit.

X

 

 

 

 

 

 

 

HW OVERSPEED

Hardware detected overspeed.

X

 

 

 

 

 

 

 

PRECHARGE PROTECTION

Stop PWM when large voltage differential exists

X

 

 

 

between internal and external bus.

 

 

 

BUS CURRENT OFFSET

DC current sensor error.

X

 

 

 

 

 

 

 

S - Indicates a Certified Service Provider will be required to reset system.

NOTE

If a fault recurs after being cleared by the operator, and the condition persists, contact your Liebert technician.

Faults that initiate an AUTOSHUTDOWN include: MISER, RUNOUT, PWR SPLY VOLT (at high speed), and will require Service level and higher to reset.