UPS Interconnection Kits

Appendix A.5.5 Single Liebert FS on UPS DC Bus

The following Liebert FS Software Control Parameters must be set when a single Liebert FS is con- nected alone on the DC bus of the Liebert HiPulse UPS system.

NOTE

The Software Control Parameter values specified below must be used unless otherwise specified by the Liebert-certified service technician at Initial System Startup.

Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters Setup at Initial System Startup.

Table 29 Liebert FS Software Control Parameter settings

Liebert FS Software Control Parameter

Setting

Charge Voltage

436 VDC

 

 

Regulation Voltage

426 VDC

 

 

Vreg Delta

0 VDC

 

 

Maximum Charge Current

See Table 30

 

 

Charge Amps/Volts

See Table 30

 

 

Table 30 Liebert FS Software Control Parameters varying with UPS size

UPS Output Rating (kVA)

80

120

Liebert FS Maximum Charge Current (A)

39

50

 

 

 

Liebert FS Charge Amps/Volts (A/V)

4

5

 

 

 

Appendix A.5.6 Single Liebert FS in Parallel with Battery Pack on UPS DC Bus

The following Software Control Parameters must be reset when the Liebert FS is connected in paral- lel with a battery pack on the DC bus of the Liebert Hipulse UPS system.

NOTE

The Software Control Parameter values specified below must be used unless otherwise specified by the Liebert-certified service technician at Initial System Startup. These values may require adjustments due to the battery type.

Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters Setup at Initial System Startup.

Table 31 Liebert FS Software Control Parameter settings

Liebert FS Software Control Parameter

Setting

Charge Voltage

436 VDC

 

 

Regulation Voltage

426 VDC

 

 

Vreg Delta

0 VDC

 

 

Maximum Charge Current

See Table 32

 

 

Charge Amps/Volts

See Table 32

 

 

Table 32 Liebert FS Software Control Parameters varying with UPS size

UPS Output Rating (kVA)

80

120

 

 

 

Liebert FS Maximum Charge Current (A)

39

50

 

 

 

Liebert FS Charge Amps/Volts (A/V)

4

5

 

 

 

98