UPS Interconnection Kits

Appendix A.4.4 Liebert FS Configuration - Single Liebert FS on Series 300 DC Bus

The following Software Control Parameters must be reset when the Liebert FS is connected to the DC Bus of the Liebert Series 300 UPS system.

NOTE

The Software Control Parameter values specified below are recommended. These values may require adjustments due to the battery type. These must be used unless otherwise specified by the Liebert-certified service technician at initial system startup.

Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System Startup.

Table 26 Liebert FS Software Control Parameter settings

Liebert FS Software Control Parameter

Setting

 

 

Charge Voltage

395VDC

 

 

Regulation Voltage

385VDC

 

 

Vreg Delta

0VDC

 

 

Maximum Charge Current

See Table 27

 

 

Charge Amps/Volts

See Table 27

 

 

Table 27 Liebert FS Software Control Parameters varying with UPS size

UPS Output Rating (kVA)

10

15

20

30

40

50

65

75

100

125

 

 

 

 

 

 

 

 

 

 

 

Liebert FS Maximum Charge Current (A)

5

8

10

16

21

26

34

39

50

50

 

 

 

 

 

 

 

 

 

 

 

Liebert FS Charge Amps/Volts (A/V)

0.7

1.1

1.4

2.1

2.8

3.5

4.5

5.2

6.7

6.7

 

 

 

 

 

 

 

 

 

 

 

Appendix A.4.5 Liebert FS Configuration - Multiple Liebert FS Units on Liebert Series 300 DC Bus

Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected in parallel on the DC bus of a Liebert Series 300 UPS system for proper operation with longer run times or higher backup power requirements.

Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System Startup.

NOTE

In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales representative to arrange a review of the application.

NOTE

Your Liebert-certified service technician will configure the Software Control Parameter values at initial system startup depending on the number of paralleled units.

95