Installation

The AC wire is field-supplied. Wire size and installation must comply with all applicable local, regional and national regulations (e.g., National Electric Code for USA). An 18 AWG cable (approxi- mate metric equivalent: 0.82mm2 wire section) is recommended for this connection.

Figure 32 shows the auxiliary power fused disconnect and terminals 1, 2 and 3, the landing points for the AC wire on the Liebert FS side. Open the circuit while wiring, check the fuses and close after- wards when ready to test or start up Liebert FS.

Figure 32 Auxiliary power fused disconnect with connection points for AC wire

Terminal 1

Neutral

Terminal 3

Ground

Terminal 2 Line

Fused disconnect

The AC wire should be pulled from the left (top access recommended) and through the rear top access panel (see Figure 33). Run the AC wire along the underside of the top cabinet frame rail from the rear to the front of the cabinet. Terminate the AC wire at the fused disconnect (pictured in Figure 32; see also Figure 26).

Figure 33 Top access panel

Top access panel for AC auxiliary power supply connections

Front of Liebert FS