Emerson IFT9701 instruction manual 2Compartment tags and lockout device, 2.3Jumper settings

Models: IFT9701

1 90
Download 90 pages 24.24 Kb
Page 16
Image 16
Figure 2-2 Compartment tags and lockout device

Getting Started continued

Figure 2-2 Compartment tags and lockout device

 

Circuit board

 

compartment

Field wiring

Rated EEx d

compartment

 

Rated EEx e

 

Label 1

Label 2

 

 

Sensor wiring

Lockout device

compartment

Rated EEx i

Loosen and rotate

 

before opening

 

circuit board

 

compartment

 

2.3Jumper settings

Unless otherwise specified on the order, jumpers are set so the transmitter generates downscale fault outputs and enables flowmeter configuration. If jumper settings need to be changed, the procedure should be performed before the transmitter is installed.

To access security and fault output jumpers, unscrew the circuit board compartment cover.

If the transmitter is approved by ATEX as flameproof, the compartment has a lockout device. See Figure 2-2. The lockout device must be loosened and rotated before the compartment cover can be unscrewed.

2.3Jumper settingsManual backgroundManual background CAUTION

Improper handling of transmitter components can damage the transmitter.

If a breaker bar is used for loosening the cover of the circuit board compartment:

-Apply steady pressure to avoid chipping the paint on the transmitter housing. Chipped paint can result in corrosion of the housing. If paint becomes chipped, repaint the housing.

-Do not apply too much pressure. Excessive torque can damage the pipeline, transmitter, or sensor.

To prevent electrostatic discharge, wear an anti-static wrist strap while setting jumpers.

8

Model IFT9701 Transmitter Instruction Manual

Page 16
Image 16
Emerson IFT9701 instruction manual 2Compartment tags and lockout device, 2.3Jumper settings