Emerson IFT9701 5Shielded cable, 6Armored cable, 1Temperature ranges for jacket material

Models: IFT9701

1 90
Download 90 pages 24.24 Kb
Page 23
Image 23
Figure 3-5 Shielded cable

Remotely Mounting the Transmitter continued

Figure 3-5 Shielded cable

Outer jacket

Tin-plated copper braided shield

Foil shield (1)

Inner jacket

Drain wire (4)

Figure 3-6 Armored cableTable 3-1 Temperature ranges for jacket material Foil shield (4)

Filler (5)

 

 

 

Minimum bend radii

 

 

Static

Under

 

Outside

(no load)

dynamic

Jacket

diameter

condition

load

material

inches (mm)

inches (mm)

inches (mm)

 

 

 

 

 

PVC

0.525 (14)

4

1/4 (108)

8 1/2 (216)

 

 

 

 

 

Teflon®

0.425 (11)

3

1/4 (83)

6 3/8 (162)

FEP

 

 

 

 

Before You Begin

Figure 3-6 Armored cable

Outer jacket

Stainless steel braided shield

Foil shield (1)

Inner jacket

Drain wire (4)

Jacket materialLow operating temperature limit Foil shield (4)

Filler (5)

 

 

 

Minimum bend radii

 

 

Static

Under

 

Outside

(no load)

dynamic

Jacket

diameter

condition

load

material

inches (mm)

inches (mm)

inches (mm)

PVC

0.525 (14)

4

1/4 (108)

8 1/2 (216)

Teflon®

0.425 (11)

3

1/4 (83)

6 3/8 (162)

FEP

 

 

 

 

Getting Started

Mounting the Remote

Table 3-1 Temperature ranges for jacket material

Jacket material

Low operating temperature limit

High operating temperature limit

 

 

 

PVC

–40 °F (–40 °C)

221 °F (105 °C)

 

 

 

Teflon® FEP

–76 °F (–60 °C)

302 °F (150 °C)

 

 

 

Table 3-2 Cable selection guidelines

Installation requirements

Jacketed cable

Shielded cable

Armored cable

 

 

 

 

Conduit is used



 

 

 

 

 

 

Conduit is not used

 



 

 

 

 

 

Conduit is not used and

 

 



mechanical protection is required

 

 

 

 

 

 

 

Transmitter

Power Supply and Output Wiring

Model IFT9701 Transmitter Instruction Manual

15

Page 23