Configuration with ProLink II Software continued

Table 7-2 Effect of flow direction on outputs and totalizers

Fluid flow

Output or

Flowmeter configuration

 

 

 

 

direction

totalizer

Forward

Reverse

 

 

 

 

Fluid flowing

Milliamp output

Output increases as flow rate

Output goes to 3.8 mA

in same direction

 

increases

 

as flow arrow

 

 

 

Pulse output

Output increases as flow rate

Output remains at 0 Hz

on sensor

 

increases

 

 

 

 

 

 

 

 

 

Internal totalizers

Flow totals increase

Flow totals remain constant

 

 

 

 

Fluid flowing

Milliamp output

Output goes to 3.8 mA

Output increases as flow rate

in opposite direction

 

 

increases

from flow arrow

 

 

 

Pulse output

Output remains at 0 Hz

Output increases as flow rate

on sensor

 

 

increases

 

 

 

 

 

 

 

 

Internal totalizers

Flow totals remain constant

Flow totals increase

 

 

 

 

6.Internal damping filters out noise or the effects of rapid changes in the variable without affecting measurement accuracy.

The damping value is the filter coefficient that approximates the time required for the output to achieve 63% of its new value in response to a step change at the input. The actual time depends on many factors, including sensor type and density of the process fluid. The meter rounds down the chosen damping value to the nearest programmed filter coefficient. Programmed filter coefficients, in seconds, are:

0.1 0.2 0.4 0.8 1.6 3.2 6.4 12.8

If desired, enter an internal damping value into the Damping text box in the Flow panel.

Flowmeter Startup

Configuration with Communicator

Configuration with ProLink II

Troubleshooting