Table 4-1 Wire guidelines for DC power supply

Power Supply and Output Wiring continued

Table 4-1 Wire guidelines for DC power supply

Wire size

Wire length

 

 

 

16

AWG (1,5 mm²)

1500 feet (450 meters)

 

 

 

18

AWG (0,75 mm²)

1000 feet (300 meters)

 

 

 

20

AWG (0,5 mm²)

600 feet (200 meters)

 

 

 

4.4Connect output wiring

Figure 4-2 shows the milliamp and pulse output terminals.

Install twisted-pair, shielded cable, consisting of 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²) wire.

For basic information on milliamp output wiring, see Section 4.4.1.

For instructions on connecting the milliamp output to a Bell 202 multidrop network, see Section 4.4.2.

For instructions on connecting a HART device to the milliamp output, see Section 4.4.3.

For instructions on pulse output wiring, see Section 4.4.4.

Figure 4-2 Output wiring terminals

Active milliamp output

Passive pulse output

Internally powered

Requires pull-up resistor

 

to external 5–30 VDC

 

power supply

Conduit opening for output wiring

Wire size Field wiring compartment

 

Sensor wiring

Case ground

compartment

Terminate output cable shielding at gland or conduit fitting.

360° termination of shielding is not necessary.

Do not terminate shield inside wiring compartment.

The pull-up resistor must be of sufficient value to limit the total loop current to less than 500 ohms. Refer to Section 4.4.4 to determine the pull-up resistor needed.