Power Supply and Output Wiring continued
Table 4-1 Wire guidelines for DC power supply
Wire size | Wire length | |
|
|
|
16 | AWG (1,5 mm²) | 1500 feet (450 meters) |
|
|
|
18 | AWG (0,75 mm²) | 1000 feet (300 meters) |
|
|
|
20 | AWG (0,5 mm²) | 600 feet (200 meters) |
|
|
|
4.4Connect output wiring
•Figure 4-2 shows the milliamp and pulse output terminals.
•Install twisted-pair, shielded cable, consisting of 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²) wire.
•For basic information on milliamp output wiring, see Section 4.4.1.
•For instructions on connecting the milliamp output to a Bell 202 multidrop network, see Section 4.4.2.
•For instructions on connecting a HART device to the milliamp output, see Section 4.4.3.
•For instructions on pulse output wiring, see Section 4.4.4.
Figure 4-2 Output wiring terminals
Active milliamp output | Passive pulse output |
Internally powered | Requires |
| to external |
| power supply |
Conduit opening for output wiring
Field wiring compartment
| Sensor wiring |
Case ground | compartment |
•Terminate output cable shielding at gland or conduit fitting.
•360° termination of shielding is not necessary.
•Do not terminate shield inside wiring compartment.