Emerson IFT9701 instruction manual 2Power supply connections, 8.5Wiring

Models: IFT9701

1 90
Download 90 pages 24.24 Kb
Page 68
Image 68
Figure 8-2 Power supply connections

Troubleshooting continued

Figure 8-2 Power supply connections

¾-inch NPT or M20

 

conduit opening

 

Seal opening with

 

conduit seal or

Power supply

cable gland

terminals

External case

 

ground screw

Voltage label

 

Internal ground

Match power supply to

voltage specified on label

screw

 

7.Make sure the power cable is not installed in the same conduit or cable tray as output wiring.

8.Make sure the meter is properly grounded. If national standards are not in effect, adhere to this standard:

For grounding, use copper wire, 14 AWG (2,5 mm²) or larger wire size.

Either the internal ground screw or external case ground screw may be used as required by local policy or code.

Keep all ground leads as short as possible.

Flowmeter must be grounded with less than 1 ohm impedance.

Connect power-supply ground directly to earth.

The flowmeter does not have replaceable fuses for the power supply.

8.5Wiring

For detailed wiring instructions, refer to Chapters 3 and 4.

Wiring problems are often incorrectly diagnosed as a faulty sensor. At initial startup of the transmitter, always check the following:

1.Proper cabling, and use of shielded pairs

2.Proper wire termination

Wires on correct terminals.

Wires making good connections with the terminal strip.

Wires making good connections at the receiving device.

Wires making good connections at the sensor terminals. Table 8-3lists terminal designations for Micro Motion sensors.

60

Model IFT9701 Transmitter Instruction Manual

Page 68
Image 68
Emerson IFT9701 instruction manual 2Power supply connections, 8.5Wiring