15 Ethernet interface
14.5.2.Parameters of the channels
HEADER |
| PARAMETERS | EXAMPLES | |
CHAnnel | P1 |
|
| CHAN B3 |
| Defines the CHANNEL to be modified by the following commands | A modification of the channel 3 of the | ||
|
|
|
| board B has been chosen |
| P1 | = channel choice (A1,A2, etc? |
|
|
|
|
| ||
CHAnnel ? | Returns the selected channel number and its value |
| ||
|
|
|
| |
VALID | P1,P2 |
| VALID ALL,OFF;CHAN A1 ON;CHAN | |
|
|
|
| LOG,ON |
| Defines the channel validity |
|
| |
| P1 | = ALL for all the channels |
|
|
|
| A1,A2, etc... For each channel | Valid channel A1 and logical channels | |
|
| LOG for logical channels |
|
|
| P2 | = ON or OFF |
|
|
VALID ? | Return sthe validity of all the channels |
| ||
NAMe | P1 |
|
| CHAN B3;NAM 'oven1' |
| Modify the CHANNEL name |
|
| |
| P1 | = name ( maximum 26 caracteres ) beetween " or ' |
| |
|
|
|
| |
NAMe ? | Returns the CHANNEL name |
|
| |
|
|
|
|
|
TYPe:VOLtage | P1 |
|
| TYPE:THERM K,COMP |
| Modify CHANNEL type to voltage |
| Use of a compensated thermocouple K | |
| P1= DC or RMS |
|
| |
|
|
|
| |
TYPe:SHUNT | P1,P2 |
|
| |
| Modify CHANNEL type to current shunt |
| ||
| P1 | = DC or RMS |
|
|
| P2 | = S1M,S10M,S01,S1,S10,S50 | ( for 1mOhm, 10mOhm ,0.1 |
|
| Ohm, ... 50 Ohm) |
|
| |
| Modify CHANNEL type to frequency |
| ||
TYPe:FREQ |
| |||
| P1,P2 |
|
| |
TYPe:PT100 |
|
| ||
| Modify CHANNEL type to PT100 |
|
| |
| P1= W2, W3, W4 for 2 wires, 3 wires or 4 wires |
| ||
| P2= Resistor value ( in 1/10 of ohms) |
| ||
|
|
|
| |
TYPe:THErmo | P1,P2 |
|
| |
| Modify CHANNEL type to thermocouple |
| ||
| P1= Thermocouple = J,K,T,S,B,E,N,W |
| ||
| P2= NOCOMP or COMP |
|
| |
TYPe ? | Returns the type of CHANNEL |
|
| |
|
|
|
|
|
UNIt | P1 |
|
| UNIT CEL |
| Temperature unit for types thermocouple and PT100 | Unit Celsius degree | ||
| P1: CEL,FAR,KEL |
|
| |
UNIt ? |
|
| ||
Returns the temperature unit of CHANNEL |
| |||
|
|
|
|
|
FILter | P1 |
|
| FILTER 10HZ |
| Defines the filter of CHANNEL |
|
| |
| P1 | = WOUT,F10KHz,F1KHz,F100Hz,F10Hz, F1Hz,F10S,F100S or |
| |
| F1000S |
|
| |
|
|
|
| |
FILter ? | Returns the filter of CHANNEL |
|
| |
|
|
|
| |
RANge | P1,P2,P3 |
| RANGE 12,3,0 | |
| Modify the range and the center (zero) of CHANNEL | range = 12 Volts | ||
|
|
|
| center = 3 Volts |
| P1 | = range in ISO unit (Volts or | ) in real number |
|
| P2 | = center in ISO unit in real number |
| |
| P3 | = Position in % |
|
|
RANge ? | Returns the range and the center of CHANNEL |
|