GE P485 instruction manual Memory Map, Address Contents Access

Models: P485

1 76
Download 76 pages 55.38 Kb
Page 20
Image 20

DATA EXCHANGE

 

PLC memory

 

 

I/O inputs

I/O outputs

 

 

Current Ia

CT PRIMARY

 

The PLC exchanges data

 

 

The PLC exchanges data

via the Profibus network

 

 

via the Profibus network

between its internal input

 

 

between its internal output

area and the input area

 

 

area and the output area

of the P485

Profibus network

 

of the P485

 

 

 

 

Internal memory buffer

 

 

of the P485

 

 

Input data area

Output data area

General data area

0x0000

0x0200

0x0400

 

Current Ia

CT PRIMARY

 

The data in the input area of the P485 contains data received from nodes on the Modbus sub-network (sent in to the P485 from the sub-network)

The data in the output area of the P485 contains data received from Profibus. In this case, it is the CT PRIMARY setting of the PQMII meter.

Modbus sub-network

Modbus slave (e.g. PQMII)

CT PRIMARY setting

Current Ia actual value

Figure 3-2: Data exchange overview

Memory Map

MEMORY LOCATIONS When configuring the sub-network, use the memory locations shown below:

Address

Contents

Access

 

 

 

0x0000 to 0x0001

Status register

read/write

 

 

 

0x0002 to 0x00F3

Input data area

read/write

 

 

 

0x00F4 to 0x01FF

Reserved

-

 

 

 

0x0200 to 0x0201

Control register

read only

 

 

 

0x0202 to 0x02F3

Output data area

read only

 

 

 

0x02F4 to 0x03FF

Reserved

-

 

 

 

0x0400 to 0x7FF

General data area

read/write

 

 

 

3–2

P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

Page 20
Image 20
GE P485 instruction manual Memory Map, Address Contents Access