Hardwire Zones

Installation Instructions

Hardwire Zones

Normally Open Zones/ Normally Open EOLR Zones

1.Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device.

2.Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

Normally Closed Zones/Normally Closed EOLR Zones

1.Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device.

2.Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

NOTES

EOLR: If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone.

UL For UL commercial burglar alarm installations, use EOLR zones.

Smoke Detectors

4-Wire Smoke Detectors

Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to any zone as shown below. This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204), or on-board trigger to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information.

 

 

 

 

Figure 7. 4-Wire Smoke Detector Connections

 

_

 

+

5

 

 

 

 

 

 

 

 

 

 

RELAY

 

 

 

 

 

 

 

AUX PWR

PROGRAM

 

BLK

+

RED

 

 

 

 

RELAY

 

 

 

 

 

 

 

 

OUTPUT

AS ZONE

 

 

 

EOL

AUX PWR (+)

5

 

 

TERMINALS

TYPE 54

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

(FIRERESET)ZONE

 

 

N.O.

SUPERVISION

TO OUTPUT 17 ( )

_

BLK

+

 

4

 

 

 

RELAY MODULE

PROGRAM OUTPUT 17

 

 

 

 

 

N.C.

 

 

A77-716B.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOR "OUT NORM

 

 

 

 

CONTACT OPENS

 

 

 

USE N.O.

 

 

 

 

 

 

 

LOW" = YES IN 79 MENU

 

 

 

 

 

 

 

CONTACT,

+

 

 

N.O.

MOMENTARILY UPON

+

 

 

 

 

FIRE ALARM RESET

 

VIOLET

WHICH CLOSES

MODE AND AS ZONE

 

 

 

VIOLET

 

 

4-WIRE SMOKE

 

 

WHEN POWER

TYPE 54 IN

4-WIRE SMOKE

 

 

 

 

 

 

IS APPLIED.

80 MENU MODE

OR COMBUSTION

 

 

 

 

 

OR COMBUSTION

 

 

 

 

 

 

 

 

 

DETECTOR

2000

 

 

 

 

DETECTOR

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OHMS

 

 

 

 

 

OHMS

 

 

 

 

 

 

 

 

 

 

 

 

 

EOLR

 

 

 

 

 

EOLR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO ZONE TERM. (+)

 

 

 

-V0

TO ZONE TERM. (+)

 

 

 

 

 

 

 

-007

 

 

 

 

 

 

HEAT

 

 

 

HEAT

 

 

 

TO ZONE TERM. ( )

 

 

wiresmk

TO ZONE TERM. ( )

 

 

 

 

DETECTOR

 

 

 

 

DETECTOR

 

 

 

 

 

 

 

 

4

 

 

 

 

 

RED

EOL

 

POWER

 

SUPERVISION

 

RELAY MODULE

 

A77-716B.

 

USE N.O.

 

CONTACT,

 

WHICH CLOSES

 

WHEN POWER

 

IS APPLIED.

V0

 

4 wiresmk-008-

4-Wire Smoke Detector Using Relay for Power Reset

4-Wire Smoke Detector Using Output 17 for Power Reset

NOTES

Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger again, the control will disregard the first trigger, and no alarm signal will occur. This feature eliminates false alarms due to electrical or physical transients.

SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm Listed relay accessories must be used to reset power as described above.

Power Reset: Maximum current on trigger 17 is 100mA.

2-6