Installation Instructions

On-Board Triggers

Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip.

You can use a 4-wire cable as shown.

UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.

5-PIN TRIGGER CONNECTOR

1

KEY

3

4

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(YELLOW)

 

(RED)

(BLACK)

(GREEN)

OUTPUT 17

 

+12 AUX.

GND (-)

OUTPUT 18

4-WIRE CABLE

00-trigcon-005-V3

Figure 12.

On-Board Trigger Connector with 4-Wire Cable

NOTES

There are two on-board triggers that can be used to activate output devices.

These outputs are normally high, and go low upon programmed condition.

Outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.

Program these triggers using *80/*81 Menu modes as you would for any other relay output.

When using these outputs, note:

pin 1 = output number 17 (trigger 1):

15 ohms to ground when closed (output low), open when off (output high, normal default); can be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode,

and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay modulethat draws less than 100mA

pin 5 = output number 18 (trigger 2):

100 ohms to ground when closed (output low); open when off (output high, normal default); or can support 12V relay module that draws less than 20mA

† e.g., Altronix AX-RBS

Phone Line/Phone Module Connections

1.Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors

represent the colors of the cable to the RJ31X jack.

If using a phone module, continue with the following steps.

2.Make 12V (+) and (–) and data in and data out connections from the phone module to the control, using the connector cable supplied with the phone module, then insert the keyed connector at the other end of the connector cable into the header on the phone module.

3.Connect Phone Module terminals as shown below. Use an RJ31X jack with a direct-connect cord and make all connections exactly as shown.

4.Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset” terminals (21 & 22) on the control, as shown.

NOTES

Use 4285 or 4286 Phone Modules.

Compatibility: 4286 Phone Modules must have software version WA4286-15.1 or higher (refer to the label on the square 4286 microprocessor chip).

Only one phone module can be used.

The phone lines must be in service for the phone module to function, even when accessing the system from an on-premises phone.

If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification (AAV) section for special wiring connections.

CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for phone line connections.

2-10

Page 16
Image 16
Honeywell VISTA-10PSIA, Ademco Security Systems setup guide On-Board Triggers, Phone Line/Phone Module Connections