Installation Instructions
On-Board Triggers
Connect field wiring to the desired trigger pin on the
You can use a
UL If
1 | KEY | 3 | 4 | 5 |
| |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(YELLOW) |
| (RED) | (BLACK) | (GREEN) | ||
OUTPUT 17 |
| +12 AUX. | GND | OUTPUT 18 |
Figure 12.
On-Board Trigger Connector with 4-Wire Cable
NOTES
•There are two
•These outputs are normally high, and go low upon programmed condition.
•Outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.
•Program these triggers using *80/*81 Menu modes as you would for any other relay output.
•When using these outputs, note:
pin 1 = output number 17 (trigger 1):
15 ohms to ground when closed (output low), open when off (output high, normal default); can be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode,
and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module† that draws less than 100mA
pin 5 = output number 18 (trigger 2):
100 ohms to ground when closed (output low); open when off (output high, normal default); or can support 12V relay module that draws less than 20mA
† e.g., Altronix
Phone Line/Phone Module Connections
1.Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors
represent the colors of the cable to the RJ31X jack.
If using a phone module, continue with the following steps.
2.Make 12V (+) and
3.Connect Phone Module terminals as shown below. Use an RJ31X jack with a
4.Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset” terminals (21 & 22) on the control, as shown.
NOTES
•Use 4285 or 4286 Phone Modules.
Compatibility: 4286 Phone Modules must have software version
•Only one phone module can be used.
•The phone lines must be in service for the phone module to function, even when accessing the system from an
•If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification (AAV) section for special wiring connections.
CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for phone line connections.