*80 Menu Mode: Defining Output Functions

Use this mode to program output function definitions (up to 12 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components:

Output Definition Components

Component

Description

 

 

Output Function No.

A reference number that defines an output’s characteristics.

 

 

Activated By

Determines whether the initiating event occurs on a zone, a zone list, or a zone type.

 

 

Event

Event that triggers the output action. Can be an event occurring on a specific zone

 

number or a zone list, or a specific zone type.

 

 

Output Action

Defines the action of the relay when the defined event occurs. Can close for 2 seconds,

 

stay closed until reset, continuously pulse (1-second close-open-close-open, etc.), toggle

 

the device state, or activate for a defined duration (set in data field *177).

 

 

Output No.

Assigns this function to a specific output number (defined in *79 Menu Mode). This is

 

the output number that will perform this function upon the triggering event. Note that

 

each defined function is associated with only one output number. This means that if

 

more than one output device needs to perform this particular function, you need to

 

define another output function number with the same attributes, but assign the

 

appropriate output number. (i.e. output devices can be assigned more than one function

 

number, but each function number can only be assigned a single output number.

For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:

Prompt

Entry

Output Funct. # = 01

(assuming this is the first output function)

Activated By:

= 3 (zone number)

Enter Zn No.

= 04

(requires 2-digit zone numbers)

Output Action

= 3 (continuous pulse)

Output Number

= 02

(device mapped in *79 Menu Mode)

Start Output Definition mode by pressing 80 while in Data Programming mode.

80 Menu Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

PROMPT

 

 

 

VALID ENTRIES and EXPLANATION

 

 

 

 

 

 

 

 

Enter the output function number to be defined

 

 

Output Funct. #

 

 

 

 

 

 

 

 

01-12 = output function number

 

 

(00 = Quit)

01

 

 

 

 

 

 

 

 

[∗] to continue; 00 = exit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This screen displays a summary of the current output programming

 

 

01 A

E

Trig

 

 

 

 

 

 

 

 

A = Output Action; E = Triggering event; Trig = Trigger type

 

 

?00 0

0

– ZL=00

 

 

 

 

 

 

 

 

Question mark indicates the device shown has not been mapped. Use *79 Menu mode to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

map the device.

 

 

 

 

 

 

 

 

[∗] to continue

 

 

 

 

 

 

 

 

 

 

01 Activated By: Zone List

Select where the initiating event for this output definition is to occur.

0 = delete (deletes the output function and any previous programming)

Delete?

 

To delete this output definition, press 1.

0 = NO,

1 = YES

If you do not want to delete this output,. press 0.

 

 

 

1 = zone list (go to “A” prompt); 2 = zone type (go to “B” prompt); 3 = zone number (go to “C” prompt)

[∗] to continue

5-7

Page 43
Image 43
Honeywell VISTA-10PSIA Menu Mode Defining Output Functions, Output Definition Components, Prompt Entry, ∗80 Menu Mode