Mounting and Wiring the Control

Wiring to Keypads

1.Connect keypads to the keypad terminals as shown on the Summary of Connections diagram. Determine wire size using the Wire Run Chart below.

2.Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according to the chart at right.

3.Program the keypad addresses and sound options in data fields *190-*196. IMPORTANT: Each keypad must be assigned a unique address, starting at address 16. Keypads programmed with the same address will give unpredictable results.

Supplementary Power (optional)

1.Connect as shown. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4 (AUX –) on the control.

NOTES

• Typical Fixed-Word Display: 6150

• Typical Alpha Display: 6160

• Voice Keypads: 6150V, 6160V

• The system supports up to 8 keypads

(see program fields *190-*196).

• For single 4-wire runs, determine the current

SUPPLEMENTARY

 

CONTROL TERMINAL STRIP

POWER SUPPLY

 

 

 

 

 

 

 

 

 

+

 

AUX. AUX. DATA DATA

 

 

 

 

 

 

 

+

 

IN

OUT

 

 

 

4

5

6

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

drawn by all units, then refer to the Wiring

Run chart to determine the maximum length

that can be safely used for each wire size.

• Use supplementary power if the control’s aux.

power load for all devices exceeds 600mA.

Suggested power supply: AD12612

RED WIRE

BLK WIRE

GRN WIRE

YEL WIRE

TO KEYPAD

TO KEYPAD

TO KEYPAD

TO KEYPAD

IMPORTANT:

MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN.

TO KEYPAD BLK WIRE

TO KEYPAD RED WIRE

GRN WIRE

YEL WIRE

TO KEYPAD

TO KEYPAD

supp_pwr_supply-V0

Keypad Addresses

 

 

 

Keypad

Address

Keypad

Address

Figure 4. Using a Supplementary Power Supply

no. 1

16**

no. 5

20

 

no. 2

17

no. 6

21

 

no. 3

18

no. 7

22

 

no. 4

19

no. 8

23

 

**The first keypad is address 16, which is always enabled and set with all sounds on.

UL Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in case of AC power loss.

The battery-backed power supply should have enough power to supply the keypads with the UL required minimum standby power time.

Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad from the control’s auxiliary power output.

Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)

Wire

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

Size

50 mA or less

100 mA

300 mA

500 mA

600 mA

#22

900 ft (274m)

450 ft (137m)

150 ft (46m)

90 ft (27m)

75 ft (23m)

#20

1400 ft (427m)

700 ft (213m)

240 ft (73m)

140 ft (43m)

120 ft (37m)

#18

1500 ft (457m)

1100 ft (335m)

350 ft (107m)

220 ft (67m)

170 ft (52m)

#16

1500 ft (457m)

1500 ft (457m)

550 ft (168m)

350 ft (107m)

270 ft (82m)

*Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4285/4286 Phone Module, and LRR.

Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the current draw of that device alone.

The length of all wire runs combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.

2-3

Page 9
Image 9
Honeywell VISTA-10PSIA, Ademco Security Systems Wiring to Keypads, Supplementary Power optional, Keypad Addresses