Honeywell VISTA-10P Menu Mode Output Device Mapping, Installation Instructions, ∗79 Menu Mode

Models: Ademco Security Systems VISTA-10P VISTA-10PSIA

1 72
Download 72 pages 33.62 Kb
Page 42
Image 42
Output Device programming involves:

Installation Instructions

Output Device Programming Overview (*79/*80 Menu Mode)

Output Devices: The system supports up to 4 relays plus 2 built-in trigger outputs. These “output devices” are assigned to system-wide output numbers (01-04, 17, 18). Relays are identified by the relay module’s device address and the relay position on the module (i.e. the physical relay number, 1-4, on the module). Built-in triggers are identified by the output number, 17 for Trigger 1 and/or 18 for Trigger 2.Use *79 Menu Mode to assign output numbers and map them to device addresses.

Output Functions: The system also provides up to 12 installer-defined output functions, which can be assigned to any of the physical outputs. Therefore, the action of any one of the outputs can be based on as many of these functions as desired. This lets a single relay perform many functions. Use *80 Menu Mode to define output functions.

Relays are not recommended for life safety applications.

MENU NAVIGATION NOTE: For *79 and *80 menus, press the [] key to accept an entry and advance to the next prompt. Use the [#] key to go back to the last question if needed (to check or change an entry). Press [] to go forward again.

Output Device programming involves:

1.Use *79 Menu Mode to assign module and output numbers and map them to device addresses. NOTE: You must map output devices using *79 Menu Mode before you can use *80 menu Mode.

2.Use *80 Menu Mode to create output definitions, which control the output devices.

*79 Menu Mode: Output Device Mapping

Use this menu to assign the Relay Module device address and specific relay numbers. The system is based on predefined module addresses. The address for the 4204 is 12. Refer to the “Module Address” prompt on the next page and set the module’s address (via module DIP switches) accordingly.

Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following prompts are displayed:

79 Menu Mode

PROMPT

ENTER OUTPUT NO.

00 = QUIT

xx

VALID ENTRIES and EXPLANATION

Enter the logical (or reference) relay number as used in the system.

01-04 = relays; 17-18 = on-board triggers (can be programmed for inverted output; see next prompt).

Use the worksheet on the Programming Form (printed separately) to organize device numbers.

[∗] to continue

17 OUT NORM LOW

 

0 = NO 1 = YES

0

This prompt appears only for Triggers 17 and 18.

0 = no (standard default); sets the trigger output level normally high

1 = yes; sets the trigger output normally low (can be used for resetting 4-wire smoke detectors by connecting trigger wire to the negative power terminal of the smoke detector, selecting 1 at this prompt, and setting as zone type 54, fire zone reset, in *80 Menu mode)

[∗] to return to Output Number prompt (use *80 Menu mode to program the function of the trigger)

XXOUTPUT TYPE

DELETE?0

Enable or delete this output.

0 = delete this output number; 1 = enable output [∗] to continue

 

XX MODULE ADDR

 

Enter the module’s predefined address “12” (set the module’s DIP switches to “12”).

 

07-15

yy

[∗] to continue

 

 

 

 

 

 

 

Enter the actual (or physical) relay number, 1-4, with respect to the Relay Module upon

 

XX REL POSITION

 

 

1-4

zz

which it is located.

 

 

 

[∗] to return to the Output Number prompt for programming the next device

 

 

 

 

 

 

5-6

Page 42
Image 42
Honeywell VISTA-10P Menu Mode Output Device Mapping, Installation Instructions, Output Device programming involves, Prompt