Installation Instructions
Type 12 | • Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a |
Monitor Zone | short/open, the message, |
| zone number) will be sent to the Central Station. The system keypad will display |
| a “check” message indicating the appropriate zone (but keypad beeping does not |
| occur). Upon restoral of the zone, the message, |
| #XXX " will be sent to the Central Station. |
| • The “check” message will automatically disappear from the keypad dynamically, |
| when the zone restores; a user code + off sequence is not needed to reset the zone. |
| • Faults of this zone type are independent of the system, and can exist at the time |
| of arming without interference. |
| • Since this is a “trouble” zone type, do not use this zone type with relays set to |
| activate upon “alarm.” |
Type 14 | • Assigned to any zone with a carbon monoxide detector. |
24 Hour Carbon | • The bell output will pulse when this zone type is alarmed. |
Monoxide Monitor | • Always active and cannot be bypassed. |
Type 16 | • Provides a fire alarm when zone is shorted, but only after alarm verified. |
Fire w/Verification | • System verifies alarm by resetting zones for 12 seconds after short is detected. A |
| subsequent short circuit within 90 seconds triggers fire alarm. |
| • Provides a trouble response when zone is open. |
Type 20 | • Arms the system in Stay mode when the zone is activated. |
| • Pushbutton units send the user number to the central station when arming or |
| disarming. |
| • User number for button must be assigned. |
Type 21 | • Arms the system in Away mode when the zone is activated. |
| • Pushbutton units send the user number to the central station when arming or |
| disarming. |
| • User number for button must be assigned. |
Type 22 | • Disarms the system when the zone is activated. |
Disarm (BR only) | • User number for button must be assigned. |
|
|
Type 23 * | • Can be used on a zone when an output relay action is desired, but with no |
No Alarm Response | accompanying alarm (e.g., lobby door access). |
|
|
Type 24 | • Usually assigned to all sensors or contacts on exterior doors and windows where |
Silent Burglary | bells and/or sirens are NOT desired. |
| • Provides an instant alarm, with NO audible indication at any keypad or external |
| sounder, if the zone is faulted when the system is armed in the Away, Stay, |
| Instant, or Maximum modes. |
| • A report is sent to the central station. |
Type 77 | • Assign to zone wired to a keyswitch. |
Keyswitch | • Do not use devices assigned as input type “BR” with this zone type. |
|
|
Type 81 | • Assign to zone connected to AAV module. |
AAV Monitor Zone | • Monitors |
| - When the zone is faulted, all alarm sounding and dialer reporting stops, except |
| for fire alarms, which immediately terminate the voice session and cause |
| a fire report to be sent. |
| - When the zone is restored (session ended), sounding resumes (if bell timeout |
| has not expired) and reports that were stopped are sent. |
Types 90 | Allows for a custom zone response. Options include response to entry/exit delays, |
Configurable | response opens/shorts, types of alarm/trouble sounding, dial delay, and unique |
| Contact ID report code. |
| UL installations: Zone Type 90 may not be used as fire or burglar alarm zones on |
| fire or UL burglar alarm installations. |
*The system can still be armed when these zone types are in a faulted condition.
NOTE: All of the zone types described are available for the wireless portion of the system, if used.