Ademco Contact ID®

The Ademco Contact ID® Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selected.

1-digit event qualifier (“new” or “restore”).

3-digit event code.

3-digit zone number, user number, or system status number (see the following page).

Ademco Contact ID® Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ where:

CCCC(CCCCCC) = Customer (subscriber) ID Q = Event qualifier, where:

E = new event , and R = restore EEE = Event code (3 hexadecimal digits)

Note: For a complete list of event codes, refer to the central office receiver manual.

GG= Partition number (always sent as “01” for this control; system messages show “00.”

ZZZ= Zone/contact ID number reporting the alarm, or user number for open/close reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.

TABLE OF CONTACT ID EVENT CODES

Code

Definition

110

Fire Alarm

121

Duress

122

Alarm, 24-hour Silent

123

Alarm, 24-hour Audible

131

Alarm, Perimeter

132

Alarm, Interior

134

Alarm, Entry/Exit

135

Alarm, Day/Night

143

Alarm, Expansion Module

145

ECP Module cover tamper

146

Silent Burglary

150

Alarm, 24-Hour Auxiliary/Monitor zone

162

Carbon Monoxide

301

AC Power

302

Low System Battery/Battery Test Fail

305

System Reset (Log only)

309

Battery Test Failure

321

Bell/Siren Trouble

333

Trouble, Expansion Mod. Supervision

341

Trouble, ECP Cover Tamper

344

RF Receiver Jam

351

Telco Line Fault

353

Long Range Radio Trouble

373

Fire Loop Trouble

374

Exit Error Alarm

380

Global Trouble, Trouble Day/Night

Code

Definition

381

RF Sensor Supervision

382

Supervision Auxiliary Wire Zone

383

RF Sensor Tamper

384

RF Sensor Low-battery

393

Clean Me

401

Disarmed, Armed AWAY, Armed

 

MAXIMUM

403

Schedule Arm/Disarm AWAY

406

Cancel by User

407

Remote Arm/Disarm (Downloading)

408

Quick Arm AWAY

409

Keyswitch Arm/Disarm AWAY

441

Disarmed/Armed STAY/INSTANT,

 

Quick-Arm STAY/INSTANT

442

Keyswitch Arm/Disarm STAY

459

Recent Close (restore only)

570

Bypass

601

Manually Triggered Dialer Test

602

Periodic Test

606

AAV to Follow

607

Walk Test Entered/Exited

623

Event Log 80% Full

625

Real-Time Clock was Changed (log only)

627

Program Mode Entry (log only)

628

Program Mode Exit (log only)

642

Latch Key (log only)

750 -

Reserved for Configurable Zone Type

789

report codes (check with central station

 

when using these codes)

6-3

Page 55
Image 55
Honeywell VISTA-10PSIA, Ademco Security Systems setup guide Ademco Contact ID, Code Definition, Maximum