Rung 2 This rung initiates the process and configures the ENI module’s Serial port for 38400 Baud.
Rung 3 This rung is initiated by the Done bit of the previous MSG and it disables
BOOTP.Rung 4 This rung configures the ENI with its own IP address.Rung 5 This rung adds the IP address of the SLC 5/05 controller to the ENI module’s Message Routing table at DF1 node 1. This means that any message sent by the
Rung 6 This rung adds the IP address of the
Rung 7 This rung instructs the ENI module to save the configuration data sent to it in
The following table contains the information needed to send messages to the ENI to configure it for this example. For a complete list of ENI configurable features, please refer to Chapters 4 and 5.
Table 7.4 ENI #2 Configuration - Message Instructions ParametersConfiguration | Configuration Function | Data Type | Message Node | Message | Message Function | |
Node Number |
|
| Number | Length (bytes) |
|
|
|
|
|
|
|
| |
101 | Configure Route 1 Address | Integers | 1 | 8 | Route DF1 MSG to IP at Address 1 | |
|
|
|
|
|
| |
145 | Configure Route 45 Address | Integers | 45 | 8 | Route DF1 MSG to IP at Address 2 | |
|
|
|
|
|
|
|
248 | Save/Reset | Integer | N/A | 2 | 0 | = save configuration to flash |
|
|
|
|
|
| |
250 | TCP/IP Config. | Integer | N/A | 8 | Assign an IP Address to the ENI | |
|
|
|
|
|
|
|
252 | BOOTP | Integer | N/A | 2 | 1 | = disable BOOTP |
|
|
|
|
|
|
|
253 | Baud Rate | Integer | N/A | 2 | 6 | = 38400 Baud |
|
|
|
|
|
|
|
Publication