ENI Configuration (Node 248 to 254)

4-11

 

 

Node 248 - Save/Reset Function

Depending on the value of the Save/Reset option, the ENI performs the following operations when receiving a PCCC Unprotected Write message of one element (integer) to Node 248.

Value of

 

ENI Operation

 

 

Save/Reset

 

 

 

 

 

 

 

0

 

The ENI immediately stops all normal operations and saves the

 

 

configuration to non-volatile memory.

 

 

 

 

 

 

 

 

 

The ENI may take up to 60 seconds to complete

 

 

IMPORTANT

 

 

 

this save operation. The configuration is not

 

 

 

 

permanently saved until the Save command is

 

 

 

 

sent.

 

 

 

 

1

 

The ENI immediately stops all normal operations and performs a soft

 

 

reset.

 

 

 

 

 

2

 

The ENI immediately stops all normal operations, performs a soft

 

 

reset, and returns all parameters to their “out-of-box” settings.

 

 

 

3

 

The ENI immediately stops all normal operations, performs a soft

 

 

reset, and returns all parameters to their “out-of-box” settings (except

 

 

for the IP address, Subnet Mask, Gateway ID, and Security Mask).

 

 

 

 

 

Node 249 - From String

Node 249 holds the ASCII string that is sent with any e-mail message initiated by the ENI. Criteria for a valid E-mail From String include:

The From String remains at the default value unless changed by the user. See page 4-10for default information.

The From String must contain an “@” symbol.

The From String cannot contain any spaces or special ASCII characters.

The maximum length of the From String is 64 characters. Any additional characters are ignored.

The From String is sent from a String Table consisting of 84 characters.

To configure the From String, initiate a message with a string element as the data. The message instruction procedure is shown on page 4-8.