7-22Connecting 1769-L20 CompactLogix Controllers on Ethernet

Figure 7.25 Configure Ethernet Driver Using RSLinx

From the RSLOGIX500 programming software, you should now be able to download your SLC 5/05 program. Then, from the RSLOGIX5000 software you should now be able to download your 5550 controller program.

Once all programs are downloaded to their respective controllers, place each controller into the RUN mode and a MSG from each controller will be sent to each of the other controllers. Each controller will only send one MSG at any given time. Go online with the SLC 5/05 and 5550 controllers to verify the successful completion of their Messages.

 

You cannot go online with the -L20 controller at this

IMPORTANT

time, but you can verify that the -L20 messages are

 

 

 

completing successfully by looking at the destination

 

in the two other controllers where the -L20 is writing

 

data. Verify that the data is being received.

 

 

Publication 1761-UM006A-EN-P - February 2001