HP MicroLogix 1761-NET-ENI Message Instruction Error Codes, Error Codes Generated by the ENI

Models: MicroLogix 1761-NET-ENI

1 102
Download 102 pages 23.71 Kb
Page 81
Image 81

Troubleshooting 8-3

Error Codes Generated by the ENI

This table shows the error codes that may be generated by the ENI. A full listing of error codes that may be generated by the Message Instruction is shown below.

Error Code

Description of Error Condition

 

 

10H

Target node cannot respond because of incorrect command parameters or unsupported command. Possible causes:

 

The data size of the message is invalid.

 

The data format is incorrect for any of the supported PCCC messages.

 

Register parameters are not formatted correctly, or there is not enough data provided.

 

RS-232 configuration packet data is not the correct size.

 

The Node Address is invalid or out-of-range.

 

The distant ENI, controller, or device may not be responding.

 

There may be a break in the connection between the ENI devices or controllers.

 

BOOTP/DF1 parameter is invalid.

 

 

30H

PCCC Description: Remote station host is not there, disconnected, or shutdown.

 

 

D0H

One of the following:

 

No IP address configured for the network or ENI not configured for Node Address used.

 

Bad command - unsolicited message error.

 

Bad address - unsolicited message error.

 

No privilege - unsolicited message error.

 

 

Message Instruction Error Codes

When the controller detects an error during the transfer of message data, the controller sets the ER bit and enters an error code that you can monitor from your programming software.

Error Code

Description of Error Condition

 

 

02H

Target node is busy. NAK No Memory retries by link layer exhausted.

 

 

03H

Target node cannot respond because message is too large.

 

 

04H

Target node cannot respond because it does not understand the command parameters OR the control block may have been

 

inadvertently modified.

 

 

05H

Local processor is off-line (possible duplicate node situation).

 

 

06H

Target node cannot respond because requested function is not available.

 

 

07H

Target node does not respond.

 

 

08H

Target node cannot respond.

 

 

09H

Local modem connection has been lost.

 

 

0BH

Target node does not accept this type of MSG instruction.

 

 

0CH

Received a master link reset (one possible source is from the DF1 master).

 

 

10H

Target node cannot respond because of incorrect command parameters or unsupported command.

 

 

12H

Local channel configuration protocol error exists.

 

 

13H

Local MSG configuration error in the Remote MSG parameters.

 

 

Publication 1761-UM006A-EN-P - February 2001