For thermal considerations, the x440 must be installed with perforated doors on both front and back. Do not install the x440 in a rack with a glass front door.
Although installation is supported in
The maximum weight of the system, depending on your configuration, is 50 kg (110 lb.). Therefore, this system requires two people to install it in a rack.
If you use a
Make sure all the cables attached to the x440 are long enough to permit the server to be slid out of the rack. This would include the normal cables such as power, network, and fiber cables, but also includes the Remote I/O cable for connecting to the
Since the x440 is rack optimized, the IBM xSeries rack configurator should be used to ensure correct placement. The configurator can be downloaded from:
For EMEA: http://www.pc.ibm.com/europe/configurators/
For USA: http://www.pc.ibm.com/us/eserver/xseries/library/configtools.html
For other countries or regions:
a.Go to http://www.ibm.com
b.Click Select a country
c.Select your country
d.Click Products and Services
e.Click Intel-based servers
f.Click Tools
g.Scroll down to find the Rack Configurator section
3.8Power considerations
The x440 ships with two redundant,
Chapter 3. Planning 103