2.4 Analog inputs

SCOM-100 has 2 built in analog inputs (AI1, AI2). A1 is designed for voltage input and A2 for current input.

2.4.1 Analog input 1

Analog input 1 is a voltage input with two wiring options.

Wiring option: A1A

The input voltage range for this wiring option is 0-1VDC. The input resistance is 2K. The input voltage range is converted internally to a digital raw range of 0-4095.

The circuit displayed on the left side of the page uses a monolithic semiconductor sensor (AD592) for temperature measurement. This sensor acts as a high impedance temperature dependent current source of 1µA/K. The nominal current output is 298µA at 25°C. The voltage drop on the analog input resistor (2K) is 496mV at -25°C and 756mV at 105°C. The SCOM-100 power supply (Vcc) can be used for the sensor’s excitation.