SCOM-100, User guide 62
Cmd Description Syntax Comments
1201 Set AI Alarm
Messages
cmd,m,n,id1,id2 m:0-4, n:1-2 (base)
or 1-4 (ext),
id1/id2:0-128
1210 Clear AI
Configuration
cmd,m,n m:0-4, n:1-2 (base)
or 1-4 (ext)
1800 Set analog IN
deadband
Cmd,d D:0-5% of the total
scale with 0.1 steps
9.1.5 I/O Functions
Cmd Description Syntax Comments
1250 Set ON/OFF
- PID Control
Configuration
cmd,id,m,n,m
1,n1,sp,g,it,dt,
ct,h
id:1-4, m,n:AI,
m1,n1:DO,
sp:-100000-100000,
g:0.0-100.0,
it:0-1000 sec,
dt:0-200 sec,
ct:1-15 min,
h:0.0-20.0 %
1251 Set ON/OFF
- PID Control
state
cmd,id,s id:1-4, s:0-1
1252 Set PID
Control DI
cmd,id,m,n id:1-4, m:0-8, n:1-4
1253 Clear PID
Control DI
cmd,id id:1-4