SCOM-100, User guide

37

ALH:

Alarm high limit in physical units

 

(number in the range of SCL to SCH

 

with one optional decimal digit.

 

Example: ALH = 121.5)

u:

Physical unit (0-15 characters)

d:

Delay time in seconds (0-65535)

For example let us explain all the different parameter settings to use a 4-20mA, 0-10 bar pressure sensor wired on analog input 2 on the main unit (See section 2.4.2).

The pressure sensor characteristic is shown in the diagram below:

The 4-20mA input signal is converted by the internal A/D converter in the digital raw range of 819 to 4095.

Page 37