SCOM-100, User guide 39
1200,0,2,Pressure,819,4095,0,10000,2500,
8500,mBar,15
The low alarm limit is set to 2.5 Bar, the high alarm limit
to 9.5 Bar. A 15 second delay is also set so that the input
signal must persist in value and exceed alarm limits (low
or high) for 15 seconds. If these clauses are met then an
alarm SMS will be initiated.
Note: Alarm annunciation is cancelled if the respective
Scale (low or high) and limit alarm values (low or
high) are equal.
4.5.2 Setting alarm message’s texts for analog inputs
A similar command to the one for digital inputs is
available to associate low and high alarm events with
respective SMS messages (1-128 messages, see 4.3.1).
The configuration command is:
1201,m,n,ID1,ID2
1201: Command ID
m: Module number (0 for SCOM-100 main
unit, 1-4 for AI-4 expansion units)
n: Input number (1-2 for SCOM-100 main
unit, 1-4 for AI-4 expansion units)
ID1: ID number 0-128 of the message’s text
for exceeding the low limit
ID2: ID number 0-128 of the message’s text
for exceeding the high limit
Note: ID1/ID2 value 0 means no message.